10 kV小電阻接地系統(tǒng)的參數(shù)特點及其短路計算

申請免費試用、咨詢電話:400-8352-114

摘 要:
介紹了10kV小電阻接地系統(tǒng)的特點,采用對稱分量法對單相接地故障進行了序網(wǎng)分析,在給定的初始參數(shù)條件下,提出了小電阻接地系統(tǒng)參數(shù)的一些特點,并作了分析計算,得出單相接地故障時系統(tǒng)線電壓仍維持平衡的結(jié)論。最后對有關(guān)接地設(shè)備的選擇給出了計算方法。
關(guān)鍵詞:中性點小電阻接地;對稱分量法;短路計算

Parametric attributes of 10 kV power system grounded by small resistance and its short-circuit calculation
Abstract:The features of 10 kV distribution system grounded by small resistance are described in this paper.The sequential network analysis of single-phase earth fault is conducted using the symmetrical component method.Given initial parameters,some parametric attributes of such system are presented along with analytical computation.It draws a conclusion that the line voltage of the system remains balanced in spite of single-phase ground faults.The computing method for selecting relevant grounding apparatus is proposed at last.
Key words:neutral grounding by small resistance;symmetrical component method;short circuit calculation
  中性點經(jīng)小電阻接地的配電系統(tǒng)在城市電網(wǎng)中已越來越廣泛地被采用。部分城市電網(wǎng)主要以電纜作為送電線路,且使用緊湊型的全封閉式的開關(guān)設(shè)備及氧化鋅避雷器,有些城市使用了不少耐壓標準較低的電纜。這樣的系統(tǒng)有幾個特點:a)系統(tǒng)電容電流較大,通常超過50 A,單相接地故障后會產(chǎn)生較高的內(nèi)部過電壓;b)單相接地故障概率比架空出線少得多;c)設(shè)備不允許在單相接地后約3倍的工頻過電壓下再連續(xù)運行。這樣要求當系統(tǒng)發(fā)生單相接地后應(yīng)立即切除故障線路,采用小電阻接地有利于繼電保護裝置可靠迅速地檢測并切除故障回路,小電阻接地還可改善系統(tǒng)參數(shù)減少接地故障時的內(nèi)部過電壓值。
  小電阻接地系統(tǒng)的分析計算在有關(guān)手冊及參考書中均未做深入的研究,本文嘗試在這方面進行一些分析探討。
 